Small-Goods Refrigerator Operation Checked in Parkes
Job summary
At Cunningham’s IGA in Parkes, a stand-alone small-goods refrigerator was reported to be operating at a high temperature of around six degrees. A Trimech technician checked the capacitor, identified a low-pressure cut-out using gauges, added one kilogram of refrigerant and observed the system during a ten-minute operating test.
Customer report
Cunningham’s IGA Parkes reported that a stand-alone small-goods refrigerator was sitting at a high temperature, described as around six degrees. The concern related to the operating temperature of the small-goods fridge at the Parkes retail site. The reported temperature was the reason for the service attendance.
Diagnosis & technical assessment
On arrival, the technician found the refrigerator system operating at a high temperature. The capacitor was checked and found to be operating correctly. Gauges were connected to the refrigeration system, and the technician observed that the unit was cutting out on low pressure.
Following the addition of refrigerant, the system was operated for ten minutes. During that observation period, the technician checked pressures and temperatures at the fan and coil. The technician described the system as operating well during testing. The observed low-pressure cut-out was the diagnostic finding recorded during the visit; the ten-minute assessment established only the operating condition observed at that time.
This job record is derived from first-party technician notes and internal job management systems (SimPRO).


Solutions delivered
The technician attended the Parkes site and carried out checks on the stand-alone small-goods refrigerator. After confirming that the capacitor was operating correctly and observing the low-pressure cut-out with gauges connected, the technician added one kilogram of refrigerant, described as R404 in the work notes. The system was then allowed to operate for ten minutes. Pressures and temperatures at the fan and coil were checked during this test. The technician informed the customer of the work undertaken and left the site clean and tidy.
Tools, parts & systems used
- Pressure gauges
- Capacitor check
- Pressure and temperature checks at fan and coil
- 1 kg refrigerant
- Stand-alone small-goods refrigerator

Outcome & results
During the 10-minute operating observation following refrigerant addition, the refrigerator appeared to operate well. The technician checked system pressures and temperatures at the fan and coil and informed the customer of the completed work. The technician indicated that continued operation would need to be monitored to establish ongoing performance. The outcome described here is limited to the condition observed during the on-site test.
This job record is derived from first-party technician notes and internal job management systems (SimPRO).
Repair vs replacement
For this particular attendance, the work consisted of system checks, refrigerant addition and a short operating test. The technician checked the capacitor, observed the low-pressure cut-out and then assessed operation after adding refrigerant. The recorded result relates to the 10-minute observation period rather than a demonstrated long-term repair or a decision between replacement and further repair.